Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T10PL01113
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/27/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) REMOVE TAPE AT SINGLE TO DBL WALL CONNECTION 2) PROVIDE DOOR THAT DOES NOT HIT GAS PIPING AT WATER HEATER 3) SECURE PIPING AT STOVE AND ON EXTERIOR 4) SEAL PIPE PENETRATION INTO BLDG 5) EXTEND DBL WALL TO 3' ABOVE COOLER WHEN WITHIN 10' OF INTAKE 6) PROVIDE 1" CLEARANCE FROM WOOD AT ROOF PENETRATION FROM VENT |