Permit: T10PL01074

Parcel: 12601003C

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10PL01074

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/14/2012 PLUMBING - FINAL Approved IVRS - Inspection :*
12/13/2011 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) BELOW FLOOR OK, CONNECTION TO SANITARY
2) PROVIDE A FRANK PATTERN CLEANOUT COVER OVER FLOOR CLEANOUT
3) PROVIDE A SAN TEE FOR WASH/RINSE CONNECTION IN WALL
09/16/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONNECT FLOOR SINKS TO SANITARY DRAIN OR PROVIDE AN INTERCEPTOR WITH AN INTEGRAL FLOW CONTROL
2) PROVIDE APPROVED VENTING OF BOTH FIXTURES AT 3 COMP SINK
3) USE CODE APPROVED FITTINGS, CORRECTLY INSTALLED
4) FURNCO COUPLINGS ARE NOT APPROVED IN THE WALL
5) CORRECT SLOPE AND PROVIDE CLEANOUTS AT 135 DEGREE CHANGE OF DIRECTION
6) DW FS OK
02/16/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE A CITY APPROVED PLAN ON SITE AT ALL TIMES
2) PROVIDE AN INSTALLATION THAT COMPLIES WITH MINIMUM CODE STANDARDS-PAY ATTENTION TO CODE SECTIONS 901.707.4 712.304.101.4.1.1.3, 708 , 905 AND 310 UPC 2006
3) FAILURE TO COMPLY WILL RESULT IN REINSPECTION FEES
4) NOTE: A 1" AIR GAP IS REQUIRED FOR INDIRECT WASTE PIPING 801
02/04/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLAN AND PERMIT ARE TO BE ON SITE AT ALL TIMES
12/17/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
12/15/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO ACCESS AT 9:00 AM, UNABLE TO INSPECT AFTER 10:00 AM DUE TO WORK LOAD
2) PLEASE RESCHEDULE WITH A CONTACT PHONE NUMBER SO WE CAN INSPECT BETWEEN 7:30 AM-3:00 PM
07/16/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A PLAN AND PERMIT FOR NEW FLOOR SINKS
2) ALL FIXTURES REQUIRE VENTS
3) SINKS REQUIRE CLEANOUTS
4) PROVIDE A TEST ON NEW FIXTURE PIPING
5) ONLY SANITIZE COMPARTMENT OF 3 COMP SINK MAY DRAIN INDIRECTLY
6) PROVIDE APPROVED DRAINAGE FITTINGS AS REQUIRED PER CODE
7) PERM CAP ABANDON DRAIN AT DW
8) REPLACE DAMAGE CLEANOUT PLUG