Inspection Status: Denied
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2010 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTE NUMBER EIGHT, FROM 7/8/10-CONTRACTOR TO PAY REINSPECTION FEE 2) THE PLAN YOU HAVE DOES NOT MATCH YOUR INSTALLATION, HAVE APPROVED AND REVISED PLAN ON SITE 3) WATER HEATR INSTALLATIONS DO NOT MEET CODE 4) SEE NOTE 5 FROM 7/08/10 5) SEE NOTE 4 FROM 7/09/10 |
|
| 07/09/2010 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) NOT INSTALLED PER PLAN. REVISE THE PLAN TO MATCH YOUR INSTALLATION 2) OK TO COVER UNDERGROUND-SHADING IS REQUIRED TO BE 6" OVER PIPE-FINISH SHADING PIPE 3) COMPLETE ALL PIPING 4) WAER HEATERS WILL HAVE TO BE REINSTALLED PER CODE |
|
| 07/08/2010 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOT INSTALLED PER PLAN 2) LEAK AT CONNECTION BETWEEN PEX AND PVC 3) SHADE WITH CLEAN FILL 4) WATER HEATER REPAIR/REPLACE REQUIRES A PERMIT 5) WATER HEATERS INSTALLED WITHOUT PERMITS, SOME VIOLATIONS INCLUDE: PROTECTION OF EXPOSED WATER PIPING, IMPROPER VENTING, NO T & P RELIEF DRAIN, T & P RELIEF VALVE LEAKING AND NO PROTECTION FROM ELEMENTS 6) ALL HOSE BIBS TO HAVE AVB'S 7) HOW WAS THE PIPING STERILIZED ? 8) CONTINUED NOT READYS MAY RESULT IN A REINSPECTION FEE 9) WHY THE EXTRA COIL OF PEX AT UNIT #3 ? 10) WHERE IS PIPING TO BLDG #4 ON PLAN |