Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/06/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PSI TEST NOT HOLDING REPAIR LEAK BEFORE CALLING FOR INSPECTION 2) REMOVE TAPE FROM FLUE VENT AT WATER HEATER |
|
| 07/02/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CORRECT VENT CONNECTORS TO BE VENT CONNECTION AT WATER HEATER 2) SECURE EACH JOINT WITH SCREWS 3) CODE DOES NOT ALLOW FLEXIBLE CONNECTOR FOR T & P DRAIN 4) PROVIDE MINIMUM 10 PSI TEST 5) PROVIDE LADDER FOR ROOF INSPECTION 6) INSTALL WEATHER RESISTANT PIPE SUPPORTS |