Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T10PL00945
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/24/2010 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) STAND PIPE RECEPTOR DOES NOT CONTAIN THE SPLASHING 2) INSTALL A BELL INCREASER 3) SUPPORT THE T & P DRAIN PIPE WITH A PIPE CLAMP NOT TAPE 4) YARD LINE IS OK TO COVER 5) PSI TEST IS OK 6) REMOVE GAUGE AND INSTALL PERM CAP ON PIPE NIPPLE AT GAUGE LOCATION |
|
| 06/23/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THERE ARE UNPROTECTED TOOL MARKS ON THE BELOW GRADE PIPING IN AT LEAST 2 LOCATIONS 2) PIPE IS NOT DEEP ENOUGH TO PROVIDE 12" MIN COVER AT ALL LOCATIONS 3) FLEX CONNECTORS ARE NOT ALLOWED ON T & P DRAIN LINE PER UPC 608.5 4) AN AIR GAP IS REQUIRED BETWEEN RELIEF DRAIN AND INDIRECT WASTE RECEPTOR |
|
| 06/21/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GATE INTO POOL AREA IS LOCKED-PROVIDE ACCESS 2) PIPE LOOKS SHALLOW, 12" OF COVER IS REQUIRED 3) CONNECT YARD LINE TO HOUSE AND TEST ENTIRE SYSTEM 4) WATER HEATER T & P DRAIN LINE REQUIRES CORRECTION; SLOPE, MATERIALS AND AIR GAP 5) ELECTRICAL BONDING OF GAS SYSTEM IS REQUIRED 6) CHECK TEMPERATURE AND PRESSURE RELIEF VALVE FOR PROPER OPERATION |