Permit: T10PL00881

Parcel: 133397920


Addresses:

109 S BONANZA AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10PL00881

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
06/04/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE LIST FROM 6/3/10 FOR BACKFLOW
2) SECURE SHOWER VALVE
06/03/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROPERLY INSTALLED BACKFLOW PROTECTION FOR IRRIGATION SYSTEMS ( AN AVB MAY NOT HAVE DOWN STREAM VALVES, UPC T 6-2)
2) SECURE TUBING OVER HEAD WITH SUPPORTS AS CLOSE TO 32" AS POSSIBLE
3) SECURE TUBING SO AS NOT TO RIDE ON GANG NAILSERS
4) HAS INSTALLER BEEN TRAINED TO INSTALL PED ?
5) INSULATE OR SECURE TUBING IN WALLS FOR NOISE, PEX REQUIRES 6" CLEARANCE FROM WH VENT
6) KIT ANGLE STP IS LEAKING
7) NOTE: COMPRESSION FITTINGS DO NOT USE TEF TAPE, INSTALL AS REQUIRED
8) SECURE SHOWER VALVES
9) PROVIDE 18" OF METALLIC PIPING AT ANY FUTURE SEAT CONNECTIONS (WH)