Permit: T10PL00831

Parcel: 133321010


Addresses:

562 N EVELYN AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10PL00831

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/07/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
06/04/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) 1 HR CALL PROVIDED
2) NO ONE ON SITE AT 9:15 AM, NO LOCK BOX CODE GIVEN
3) CONTINUED NO ACCESS WILL RESULT IN RE-INSPECTION FEES
4) HOME VESTERS
06/01/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TEST SHALL HOLD 10 PSI MINIMUM WITH NO LOSS OF PRESSURE
05/27/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE TEST THRU FIREPLACE VALVE INTO HEARTH OF FIREPLACE
2) REATTACH BONDING CLAMP
3) REATTACH VENT CONNECTOR TO WATER HEATER DRAFT HOOD PROPERLY
4) PROVIDE A LISTED GAS SHUT OFF VALVE FOR WATER HEATER
5) SECURE GAS PIPING IN FURNACE CLOSET
6) T & P DRAIN TO BE APPROVED MATERIAL AND GRAVITY DRAIN