Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) SECURE VENT CONNECTOR AND DRAFT COLLAR TO WATER HEATER 2) REMOVE OLD LEAKING WATER SHUT OFF VALVE 3) INSTALL COOLER SUPPLY LINE UP STREAM OF WATER HEATER S.O.V. 4) NOTE: WATER PIPING REPLACEMENT REQUIRES PERMIT |
|
| 05/24/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE FOR BOTH FURNACE AND WATER HEATER VENTS DBL WALL WITH APPROVED VENT CAPS 2) CAP OLD GAS PIPING IN FURNACE/WATER HEATER CLOSET 3) REMOVE TAPE FROM SINGLE TO DBL WALL VENT CONNECTION AT WATER HEATER VENT 4) PROVIDE BONDING OF BLDG GAS PIPING SYSTEM, #4 OR #6 COPPER WIRE-2 BONDING CLAMPS |
|
| 05/20/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DID NOT LEAVE CONTACT NUMBER WITH MESSAGE 2) WILL REQUIRE ACCESS TO ROOF AND INSIDE |