Permit: T10PL00733

Parcel: 133131470


Addresses:

7611 E LEE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/19/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
05/14/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) ALL PREVIOUS CORRECTIONS COMPLETED EXCEPT FOR #9, OBTAIN MECHANICAL PERMIT FOR THIS UNIT
2) NO GAS CONNECTION ALLOWED TO ROOF TOP UNIT UNTIL MECHANICAL PERMIT OBTAINED AND INSPECTION APPROVED
3) NOTE: GAS FLEX CONNECTOR IS UNDERSIZED AND DISCONNECTED. THIS PLUMBING PERMIT TO BE CALLED BACK IN FOR A FINAL ONCE MECHANICAL ISSUE IS RESOLVED
05/13/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
05/07/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) TEST IS BELOW 10 PSI
2) YARD PIPING COVERED WITHOUT INSPECTION
3) EXPOSE A MINIMUM OF 3' OF PIPING ON EITHER SIDE OF BELOW GROUND FITTINGS
4) SOV AT BLDG REQUIRED
5) INSTALLATION OF 150,000 BTU INSTANT HOT WILL REQUIRE RE-SIZING HOUSE PIPING, OR RUN A DEDICATED 3/4" SUPPLY
6) NOTE STOVE BTU DEMAND, ALSO NEW ROOF TOP UNIT
7) PIPE RELIEF DRAIN SEPERATELY TO APPROVED LOCATION WITH APPROVED MATERIALS AND AIR GAP
8) PIPE CONDENSATE TO AN APPROVED LOCATION WITH AIR BREAK
9) NEW ROOF TOP UNIT REQUIRES A PERMIT