Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 05/14/2010 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL PREVIOUS CORRECTIONS COMPLETED EXCEPT FOR #9, OBTAIN MECHANICAL PERMIT FOR THIS UNIT 2) NO GAS CONNECTION ALLOWED TO ROOF TOP UNIT UNTIL MECHANICAL PERMIT OBTAINED AND INSPECTION APPROVED 3) NOTE: GAS FLEX CONNECTOR IS UNDERSIZED AND DISCONNECTED. THIS PLUMBING PERMIT TO BE CALLED BACK IN FOR A FINAL ONCE MECHANICAL ISSUE IS RESOLVED |
|
| 05/13/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/07/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) TEST IS BELOW 10 PSI 2) YARD PIPING COVERED WITHOUT INSPECTION 3) EXPOSE A MINIMUM OF 3' OF PIPING ON EITHER SIDE OF BELOW GROUND FITTINGS 4) SOV AT BLDG REQUIRED 5) INSTALLATION OF 150,000 BTU INSTANT HOT WILL REQUIRE RE-SIZING HOUSE PIPING, OR RUN A DEDICATED 3/4" SUPPLY 6) NOTE STOVE BTU DEMAND, ALSO NEW ROOF TOP UNIT 7) PIPE RELIEF DRAIN SEPERATELY TO APPROVED LOCATION WITH APPROVED MATERIALS AND AIR GAP 8) PIPE CONDENSATE TO AN APPROVED LOCATION WITH AIR BREAK 9) NEW ROOF TOP UNIT REQUIRES A PERMIT |