Permit: T10PL00708

Parcel: 125041960


Addresses:

2401 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/25/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
05/17/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
05/17/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
ADDRESS 2801 IS WRONG. SHOULD BE 2401. THIS MUST BE CHANGED.
REMOVE TRAP FROM T & P DRAIN FROM WATER HEATER #1
TERMINATE T& P FROM WATER HEATER #2 TO OUTDOORS WITH DOWNBILL SLOPE.
REMOVE SINGLE WALL ELBOW FROM VENT PIPE AND USE DOUBLE WALL . SCREW SINGLE WALL VENT TO DRAFT DIVERTER
OK TO BACKFILL TRENCH
05/14/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE T & P DRAINS TO DAYLIGHT
2) GAS FLEX TO WATER HEATER NOT TO EXCEED 3' IN LENGTH
3) PROVIDE A SEDIMENT TRAP AT WATER HEATERS AND FURNACES
4) 3/8" I.D. X 18" GAS FLEX TO FURNACE NOT ADEQUATE FOR 115,000 BTU
5) WATER HEATER IN GARAGE PROVIDE 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR. EXTEND DBL WALL INTO ROOM
6) 1/2" GAS LINE TO FURNACE NOT ADEQUATE. USE 3/4"
7) PROVIDE A 15 POUND PRESSURE GAUGE