Permit: T10PL00633

Parcel: 12106245A


Addresses:

5630 E PIMA ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/17/2010 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
05/12/2010 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PSI TEST HAS DROPPED BELOW 2 PSI-CHECK FOR LEAKS AND RETEST
2) ADD MISSING SUPPORTS ON MAIN PIPING AND SECURE SUPPORT AT FURNACE VALVE LOCATION
04/23/2010 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) SUPPORT PIPING TO NEW ROOF TOP UNIT
2) PROVIDE A PERMIT FOR MECHANICAL
3) WATER HEATER FLEXES ARE REQUIRED TO BE REPLACED WHEN REWORKED PER MANUFACTURES INSTRUCTIONS