Permit: T10PL00407

Parcel: 136331020


Addresses:

9430 E 39TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
03/25/2010 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
03/17/2010 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TEST TO HOLD MINIMUM 10 PSI WITH NO LOSS OF PRESSURE FOR 15 MINUTES, TEST GAUGE AT 1.2 ONLY
2) PROVIDE ACCESS TO ROOF TOP UNIT FOR INSPECTION
3) SUPPORT AND SECURE GAS PIPING AT WATER HEATER LOCATION
4) LIST MAY NOT BE COMPLETE
5) NO ACCESS TO ROOF