Permit: T10PL00338

Parcel: 106110250

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10PL00338

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/15/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
03/12/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) I CALLED 888-8333 AND SAID I WAS ON MY WAY
2) SEE NOTE 6 FROM 3/3/10
3) A DRYER VENT IS NOT THE SAME THING AS A VENT CONNECTOR
03/03/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TYPE B VENT REQUIRED THRU CEILING WITH PROPER TERMINATION
2) SECURE VENT CONNECTOR, AND DRAFT COLLAR WITH GALV SHEET METAL SCREWS
3) PROVIDE PROPER CRIMP JOINTS
4) USE NO TAPE AT CONNECTION TO B VENT
5) PROVIDE AN APPROVED GAS SUPPLY VALVE, REMOVE OLD PLUG LOCK
6) ALSO CORRECT VENT CONNECTOR ON OTHER PREVIOUSLY INSTALLED BUT NEVER INSPECTED WATER HEATER