Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/12/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) I CALLED 888-8333 AND SAID I WAS ON MY WAY 2) SEE NOTE 6 FROM 3/3/10 3) A DRYER VENT IS NOT THE SAME THING AS A VENT CONNECTOR |
|
| 03/03/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TYPE B VENT REQUIRED THRU CEILING WITH PROPER TERMINATION 2) SECURE VENT CONNECTOR, AND DRAFT COLLAR WITH GALV SHEET METAL SCREWS 3) PROVIDE PROPER CRIMP JOINTS 4) USE NO TAPE AT CONNECTION TO B VENT 5) PROVIDE AN APPROVED GAS SUPPLY VALVE, REMOVE OLD PLUG LOCK 6) ALSO CORRECT VENT CONNECTOR ON OTHER PREVIOUSLY INSTALLED BUT NEVER INSPECTED WATER HEATER |