Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/20/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/13/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WATER HEATER ON WOOD PLATFORM REQUIRES A DRIP PAN. INSTALL WATER SOV. 2) WATER HEATER VENT MUST RISE VERTICALLY MINIMUM 5' WITH TYPE B THRU ROOF WITH FLASHING 3) CHECK WATER HEATER T & P VALVE FOR OPERATION, TERMINATE 24" ABOVE GROUND WITHOUT THREADS 4) A CITY APPROVED PIPING DIAGRAM IS REQUIRED FOR A REPIPE 5) PROVIDE FLASHINGS AT ROOF PENETRATIONS, PROPER PIPING SUPPORTS WITH CLAMPS AND ELECTRICAL BONDING OF GAS SYSTEM NOTE: NEW HEAT PUMP WILL REQUIRE A PERMIT AT TIME OF INSTALLATION, ALSO PVC IS NOT APPROVED AND A WATER REPIPE REQUIRES A PERMIT |