Permit: T10PL00284

Parcel: 134244000


Addresses:

6401 E BAYLOR DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/26/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
02/24/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE APPROVED METHOD FROM 2008 NEC FOR GROUNDING ELECTRODES FOR THSI BUILDING WHEN GALVANISED PIPE IS REPLACED WITH PLASTIC PIPING.
THE CLAMP USED ON THE GROUNDING RODS IS REQUIRED TO BE LISTED FOR DIRECT BURIAL.
PLEASE PROVIDE A LSITING FOR THSI CLAMP FOR DIRECT BURYING.