Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/24/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE APPROVED METHOD FROM 2008 NEC FOR GROUNDING ELECTRODES FOR THSI BUILDING WHEN GALVANISED PIPE IS REPLACED WITH PLASTIC PIPING. THE CLAMP USED ON THE GROUNDING RODS IS REQUIRED TO BE LISTED FOR DIRECT BURIAL. PLEASE PROVIDE A LSITING FOR THSI CLAMP FOR DIRECT BURYING. |