Permit: T10PL00201

Parcel: 133122270


Addresses:

7731 E WAVERLY ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/19/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
02/09/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) THREAD PROTECTORS MAY NOT BE USED
2) PROVIDE APPROVED PIPE COUPLINGS
3) REVISE PLAN TO SHOW FUTURE BRANCH AND FUTURE DEMAND
4) PROVIDE A 10 PSI TEST USING A GAUGE WITH 1/10 PSI INCREMENTATION
5) WRAP ALL TOOL MARKS AND SCOFF MARKS, REMOVE BRICKS
6) SUPPORT PIPING CONTINOUSLY WITH DIRT
7) PROVIDE ELECTRICAL BONDING
8) FLEX MAY NOT BE USED ON T & P DRAIN