Permit: T10PL00156

Parcel: 11711096D


Addresses:

100 N STONE AV #102


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T10PL00156

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2010 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1) CORRECTIONS MADE OK
2) OK TO COVER ALL AREAS
03/04/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) REMOVE FLOW CONTROL AT 3 COMP SINK
2) VENT FITTINGS BELOW FLOOD RIM TO BE DRAINAGE TYPE
3) TRAP ARM MAY NOT CHANGE SIZE
4) TRAP AND TRAP ARM TO BE THE SAME SIZE
5) GALVANIZED 45 DEGREE IS A PRESSURE FITTING USE DURHAM 45 DEGREE OR EQUAL
6) CLEANOUT TO BE INSTALLED ABOVE THE FLOW LINE FO THE PIPE
7) REMOVE PVC SHUT OFF VALVE
8) USE FLOW CONTROL WITH INTEGRAL VENT
9) FURNACE NOT PERMITTED IN THE BLDG
02/16/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) REVIEWED INSTALLATION REQUIREMENTS WITH MICHAEL