Permit: T10PL00138

Parcel: 10711167D


Addresses:

266 W BLACKLIDGE DR


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10PL00138

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/03/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
01/27/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE CORRECT ADDRESSING ON PERMITS
2) WATER HEATERS REQUIRE THE FOLLOWING CORRECTIONS: STURDY, APPROVED BASES, WEATHER PROTECTION ENCLOSURES, APPROVED VENTING WITH PROPER CLEARANCES
3) OPERATIONAL T & P RELIEF VALVES WITH CORRECT TERMINATIONS
4) SUPPORT PIPING
5) PROVIDE APPROVED GAS VALVES AT ALL LOCATIONS
6) PROVIDE ELECTRICAL BONDING