Permit: T10PL00135

Parcel: 121040890


Addresses:

2115 N FRANNEA DR

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
02/22/2010 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
02/11/2010 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
1. NO CHANGE FROM LAST INSPECTION
2. ALSO ATMOSPHERIC VACUUM BREAKER IS LEAKING. CORRECT & REMOVE OR RELOCATE SOLENOID VALVE, OR PROVIDE AN APPROVED BACKFLOW ASSEMBLY PROPERLY INSTALLED PER CODE.

CONTINUED DENIED INSPECTIONS MAY RESULT IN RE-FEES.
01/27/2010 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) PEX YARD PIPING OK TO COVER
2) REMOVE EXCESS FLUX FROM SOLDIER JOINTS
3) REAM ALL COPPER JOINTS AND FOLLOW ALL REQUIRED PROCEDURES PER UPC IS #3 FOR COPPER TUBE INSTALLATIONS
4) EXISTING AVB (DOWN STREAM OF NEW YARD LINE) MAY NOT HAVE VALVES DOWN STREAM
5) PROVIDE APPROVED BACKLOW PROTECTION PER UPC T 6-2