Permit: T10PL00132

Parcel: 134100350


Addresses:

7965 E SCARLETT ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/02/2010 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/28/2010 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORRECT PIPE SIZING AT UNINSPECTED PIPING ON ROOF FOR STOVE AND FURNACE BRANCH, ALSO REMOVING 1/2 RESTRICTION
2) INSTALL A FLASHING AT ROOF PENETRATION TO STOVE
3) CLAMPS ON CSST UNDER STOVE
4) SUPPORT ALL ROOF TOP PIPING MININUM 1 1/2" ABOVE ROOF
5) PROVIDE A WATER HEATER DRAIN PAN
6) PROVIDE APPROVED T & P DRAIN TERMINATION
7) SECURE/SUPPORT PIPING AT POOL HEATER
8) PROVIDE INSPECTION HISTORY OR A PERMIT FOR NEW ROOF TOP UNIT