Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) 15 PSI TEST IS OK 2) LEFT GAS CARD |
|
| 01/27/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3/8 I.D. X 24" GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE 2) EXTEND WATER HEATER VENT MIN. 3' ABOVE COMBUSTION AIR INTAKE 3) PROVIDE A NEW PRESSURE GAUGE 4) SEAL ROOF PENTRATIONS 5) PROVIDE A NEW T & P VALVE |