Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/08/2010 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/30/2010 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED COUPLING ON UNDERGROUND PIPING
2) PROVIDE ROOF JACKS FOR GAS PIPING GOING THRU ROOF
3) PROVIDE SUPPORT ON ALL GAS PIPING MINIMUM ON 1 1/2 ON ROOF
4) PROVIDE NEW PSI TEST
03/08/2010 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS PIPING MAY NOT RUN BELOW SLAB
2) UNIONS MAY NOT BE CONNECTED
3) CHECK SIZING OR PROVIDE FULL SIZE TEE AND 3/4" PIPING TO FURNACE
4) PROVIDE ELECTRICAL BONDING
5) PROVIDE CLEARANCE AROUND B VENT
6) PROVIDE PROPER CONNECTION AT WATER HEATER DRAFT COLLAR
7) B VENT IS REQUIRED TO TERMINATE ABOVE COOLER
02/23/2010 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED PIPING TO FURNACE ROOM
2) CANNOT RUN FLEX UNDER HALLWAY FLOOR
3) PROVIDE VEW PSI TEST
4) LIST MAY NOT BE COMPLETE
01/14/2010 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) TEST NOT HOLDING, PROVIDE MINIMUM 10 PSI TEST
2) NO ONE AT HOME AND GATE LOCKED