Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/17/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : PROVIDE APPROVED MATERIALS FOR T&P DRAIN PROVIDE AN AIR GAP AT TERMINATION CHECK T&P AND DRAIN FOR OPERATION CORRECT DAMAGED 6X3 TEE ON VENT CONNECTOR SECURE ALL JOINTS OF VENT CONNECTORS W/GALVANISED SHEETMETAL SCREWS. CORRECT FURNACE VENT. PROVIDE LISTED VENT INCREASER, MAKE UP JOINTS PROPERLY. DOUBLE WALL MAY NOT CHANGE BACK TO SINGLE WALL. INSTALL PER LISTING INSTRUCTIONS. |
|
| 01/12/2010 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) NEW GAS LINE OK 2) CORRECT NEW WATER HEATER AND FURNACE 3) VENT CONNECTOR AT WATER HEATER, AND VENT TERMINATION SEPERATE T & P FROM CONDENSATE AND PROVIDE TERMINATION AS REQUIRED BY CODE OR CITY OF TUCSON PETITION OF APPEAL FORM |