Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) REQUIRE A TEN POUND TEST ON THE SYSTEM (YOU HAVE 3 POUNDS). SYSTEM IS TO BE PRESSURIZED WHEN THE INSPECTOR ARRIVES. I CALLED STEVE AND GAVE A 30 MINUTE NOTICE 2) CONTINUED NOT READYS WILL RESULT IN A REINSPECTION FEE 3) I NOTICED THAT THE POINT OF CONNECTION TO EXISTING IS A TEE. THE TEE FEEDS THE WATER HEATER, AND IS NOT INCLUDED ON YOUR PLAN. 4) PIPING IS UNDERSIZED 5) WATER HEATER DOES NOT MEET CODE 6) REVISE YOUR PLAN, UPSIZE YOUR PIPE AND MAKE CORRECTIONS AT WATER HEATER |
|
| 01/06/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT INSTALLED PER PLAN, PLAN CALLS FOR 3/4" BLK IRON PIPE MAY NOT BE INSTALLED UNDERGROUND-USE SCOTCHCOAT 2) GAS PIPING REQUIRES A MINIMUM OF 12" OF COVER |