Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2011 | FIRE - FINAL | Approved | Approved 1/20/11 | |
| 12/09/2010 | FIRE - FINAL | Denied | Not approved 12/9/10 1.) The roll-up security door must be locked in the oprn position when the building is occupied 2.) The non-required exit sign is burnt out. Must repair or OK to remove from service. 3.) Remove electrical cord running through the ceiling tile. 4.) Need 6 month inspection report for the hood system. |