Permit: T10OT02569

Parcel: 12002189A


Addresses:

4010 S 12TH AV #02

Inspection Status: Denied

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
12/06/2011 FIRE - FINAL Denied 1. Need an accurate floor an site plans.
2. Exiting not up to code.
3. Refer to all items from 05/04/2011 inspection report.
05/04/2011 FIRE - FINAL Denied Not approved 5/4/11
1.) Need address numbers
a.) must be readily visible from street
b.) numbers must contrast with background color
c. must be at least 12 inches tall
2.) Need accurate floor plans. Must be approved and stamped
3.) Need minimum of 2 exits
4.) Must meet all fire code regulations for buildings requiring 2 or more exits.
a.) illuminated exit signs
b.) emergency back-up lighting
c.) door swing in direction of egress travel
d.) proper seperation between exits
5.) Can disreguard item # 4 if the occupant load is reduced to 49 people or less.
6.) All electrical wiring must meet the electrical code requirements
a.) secure all open end wiring
b.) replace all missing cover plates
c.) remove all dead or disconnected wiring
d.) secure ROMEX wiring in conduit or behind wall
e.) replace missing covers on ballast lights
7.) Only approved power adaptors are allowed to be used (must be grounded, polerized, must have a re-set button, must have power surge protection)
8.) Replace or repair missing or damaged ceiling tiles
9.) Place a "NOT AN EXIT" sign on the door leading into the seperate business
10.) Extension cords are for temporary use only
11.) Accumulation of combustibles is a fire hazard. Maintain good house cleaning practices
12.) Remove the slide bolt from glass door located in the corridor
13.) Secure compressed gas cylinders located in back room
14.) Remove gas cooking stove located in the business area of the building.
15.) Must plug the gas supply
16.) Must seperate leaving area from the business area with a one hour rated wall
17.) Must provide a 1 hour rated door between the bathroom area and the residential space.
03/28/2011 FIRE - FINAL Denied No Access