Permit: T10OT02527

Parcel: 12504243C


Addresses:

940 N OLSEN AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10OT02527

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/10/2011 FIRE - FINAL Approved Approved 2/10/11
12/28/2010 FIRE - FINAL Denied Not approved 12/28/10
1.) Need current, approved floor plans for the main area.
2.) Doors are allowed to be equipped with only one locking device. Must remove all secondary locks from any door that is part of the exiting system.
3.) Thumb-turn locks must be provided for all exit doors. Main door, optional
4.) Portable fire extinguishers, required or not, must mt be;
a.) mounted
b.) readily accessable
c.) labled
d.) serviced anually
5.) Non required extinguishers can be removed from service.
6.) Areas were extinghiushers are required
a.) Storage room area
b.) Around the water heater/ washer-dryer area
c.) kitchen area
7.) Must maintain all smoke detectors in good working order at all times.
8.) Must provide smoke detectors for tenant rooms in the upper floor area
9.) Pool gate must be readily openable from the pool side, without the use of a key at all times
10.) Directional exit signs leading to the back yard exit gate must be provided. Must be readily visible throughout pathway
11.) Maintain good housekeeping practices in areas were combustible storage can accumulate
12.) The screen cover over the exterior electrical panel must be labed, "ELECTRICAL" or "ELECTRICAL PANEL"
13.) All exit doors must be readily openable without any impediments or obstructions to full instant use at all times. Exit door, NW room, second floor, obstructed by adjacent door.
12.) Need to lable the door leading down to first level, "EXIT"