Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2011 | FIRE - FINAL | Approved | Approved 2/10/11 | |
| 12/28/2010 | FIRE - FINAL | Denied | Not approved 12/28/10 1.) Need current, approved floor plans for the main area. 2.) Doors are allowed to be equipped with only one locking device. Must remove all secondary locks from any door that is part of the exiting system. 3.) Thumb-turn locks must be provided for all exit doors. Main door, optional 4.) Portable fire extinguishers, required or not, must mt be; a.) mounted b.) readily accessable c.) labled d.) serviced anually 5.) Non required extinguishers can be removed from service. 6.) Areas were extinghiushers are required a.) Storage room area b.) Around the water heater/ washer-dryer area c.) kitchen area 7.) Must maintain all smoke detectors in good working order at all times. 8.) Must provide smoke detectors for tenant rooms in the upper floor area 9.) Pool gate must be readily openable from the pool side, without the use of a key at all times 10.) Directional exit signs leading to the back yard exit gate must be provided. Must be readily visible throughout pathway 11.) Maintain good housekeeping practices in areas were combustible storage can accumulate 12.) The screen cover over the exterior electrical panel must be labed, "ELECTRICAL" or "ELECTRICAL PANEL" 13.) All exit doors must be readily openable without any impediments or obstructions to full instant use at all times. Exit door, NW room, second floor, obstructed by adjacent door. 12.) Need to lable the door leading down to first level, "EXIT" |