Permit: T10OT02417

Parcel: 13204265B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
11/15/2010 FIRE - FINAL Approved
11/10/2010 FIRE - FINAL Denied 1. South office door requires sign: 'NOT AN EXIT'.
2. Change key lock to thumb turn dead bolt in office on North door.
3. Extension cords shall not be substituted for permanent wiring.
4. Relocatable power taps shall be directly connected to a permanent power supply.
5. Portable fire extinguishers are required: 2A 20:B C with maximum travel distance of 50 feet.