Inspection History: ELECTRIC - RECONNECT
Permit Number - T10OT02412
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2010 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
11/19/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONLY ONE CONDUCTOR PER TERMINAL LUG 2) FILL UNUSED OPENING IN SERVICE DISCONNECT 3) CLEANOUT FOREIGN MATERIAL AND DIRT FROM SERVICE DISCONNECT 4) BOND 2ND DISCONNECT ENCLOSURE 5) SERVICE DISCONNECT NOT OPERATIONAL 6) MISSING GROUNDING ELECTRODE SYSTEM AND GAS BOND |
|
11/17/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) LOCKED, NO ACCESS |
|
11/15/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |