Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2011 | FIRE - FINAL | Approved | ||
| 11/09/2010 | FIRE - FINAL | Denied | 1. MAXIMUM ALLOWABLE QUANITY: Phenolic Resin, Isopoanol and Furfuryl Alcohol Indoor Storage=660 Gallons Outdoor Storage=n/a Toluene and Acetone Indoor Storage=240 Gallons Outdoor Storage=n/a 2. Extension cords shall not be used for permanent wiring. 3. Sprinkler coverage required in office area. 4. All portable fire extinguishers must be mounted/serviced annualy. 5. Relocatable power taps shall be directly connected to a permanent power supply and an approved type (over current protection). |