Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10OT01814

Parcel: 132150190


Addresses:

821 E 47TH ST

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
02/17/2011 FIRE - FINAL Approved Approved 2/17/11
08/27/2010 FIRE - FINAL Denied Not approved 8/27/10
1.) Need address numbers for the building. 15 inches tall minimum. Numbers must contrast with background
2.) Remove the slide-bolts mounted on front glass door located in front office. (SE corner)
3.) Must remove keyed lock from same door and replace with a thumb-turn lock.
4.) Need current annual Fire Alarm System inspection report.
5.) Remove the double-cylinder lock from the door that is located next to the bathroom and is between the office and the warehouse area.
6.) Replace /repair any missing or damaged ceiling tile
7.) Secure any open-end wiring
8.) Remove the double-cylinder lock that is on the door located in rear office area
9.) The two glass door exits in the warehouse area under the mezzanine are hard to open. Must readily openable at all times
10.) Remove the keyed lock on the glass door located under the mezzanine and replace with a thumb-turn lock
6.) Replace
2.)
08/26/2010 FIRE - FINAL Cancelled Cancelled 8/26/10