Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10OT01765

Parcel: 12410001A


Addresses:

350 S PARK AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10OT01765

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2010 FIRE - FINAL Approved
09/09/2010 FIRE - FINAL Denied Not approved 9/9/10.
1.) Cover opening in wall next to front light switches.
2.) Romex wiring installed up to 7 feet from floor level must be protected with metal conduit or inside wall.
3.) Need breaker blanks fro electrical panel
4.) Extension cords are to be for temporary use only
5.) Protection method for extension cords and appliance cords on heavy traveled path must be approved.
6.) The stairs provided for the secondary exit discharge are too steep for safe exiting. The "run" and the "rise" must be a minimum of
12" run and a 7" rise
7.) Need directional exit signs directing to a public way from second exit
8.) Need a sign on the gate leading to public way reading,"GATE DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED"
9.) Need sign on the exterior side of the large sliding door reading,"DOOR BLOCKED" 6 inch tall letters, minimum.