Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10OT01751
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2010 | FIRE - FINAL | Approved | BIUILDING INSPECTOR CALLED AND STATED HE WAS OKAY WITH FIRE WALL AND EXIT DOOR. | |
08/31/2010 | FIRE - FINAL | Not ready for Inspection | If building inspector is happy with fire wall repairs and new exit door with out permits the Fire Dept. is ok. Just have building call me at 235-3646. | |
08/23/2010 | FIRE - FINAL | Denied | 1. Repair fire wall south end to 1 hour rated. 2. 2 Exits required all exit doors need to open outward. 3. Illuminated Exit signs needed over all exit doors 4. Emergency power battery back up lighting needed 1 foot candle to floor level. Will need to check and see if permit is needed to install new exit door. |