Permit: T10OT01751

Parcel: 12410001B


Addresses:

300 S PARK AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10OT01751

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/02/2010 FIRE - FINAL Approved BIUILDING INSPECTOR CALLED AND STATED HE WAS OKAY WITH FIRE WALL AND EXIT DOOR.
08/31/2010 FIRE - FINAL Not ready for Inspection If building inspector is happy with fire wall repairs and new exit door with out permits the Fire Dept. is ok. Just have building call me at 235-3646.
08/23/2010 FIRE - FINAL Denied 1. Repair fire wall south end to 1 hour rated.
2. 2 Exits required all exit doors need to open outward.
3. Illuminated Exit signs needed over all exit doors
4. Emergency power battery back up lighting needed 1 foot candle to floor level.
Will need to check and see if permit is needed to install new exit door.