Permit: T10OT01588

Parcel: 122080100


Addresses:

4158 E GRANT RD

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
08/02/2010 FIRE - FINAL Approved
07/30/2010 FIRE - FINAL Denied Not approved 7/30/10
1.) Need a sign over the main door that reads"DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED"
2.) Replace all missing cover plates
3.) Use of cube type adaptors is prohibited
4.) Remove the cross-bar security system from rear door.
5.) Secure open-end wiring in j-box east exterior wall.