Permit: T10OT01579

Parcel: 129051440


Addresses:

741 S CAMPBELL AV

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
08/20/2010 FIRE - FINAL Approved
07/26/2010 FIRE - FINAL Denied 1. Main door needs sign:" THIS DOOR TO REMAIN OPEN WHEN BUILDING IS OCCUPIED"
2. Remove all latch bolts from egress doors.
3. Replace key lock with thumb turn dead bolt on all egress doors except main exit.
4. Cover all electrical outlet boxes.
5. Exit door must open outward to street.
6. Externally or internally illuminated exit signs required.
7. Emergency egress lighting required.
8. Sprinkler sysrem must be inspected both annual and 5 year.
9. Electrical wiring must be protected.