Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2010 | FIRE - FINAL | Approved | ||
| 07/22/2010 | FIRE - FINAL | Denied | Not approved 7/21/10 1.) Repair emergency back-up light located over the main exit 2.) Provide emergency back-up lighting for the 2nd. required exit 3.) Need an illuminated exit sign over the 2nd. required exit. 4.) All secondary exit doors are required to be provided with panic hardware 5.) The small "bar room" in the back area will be treated as a seperate area with a occupant load of less then 50 6.) Provide signs indicating "Employees Only" and/or " Not An Exit" on the doors indicated 7.) Back room area security door must be kept LOCKED in the open when the building is occupied. Must provide a sign indicating as such |