Permit: T10OT01552

Parcel: 12801005H

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T10OT01552

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2010 SIGN ELECTRIC Approved IVRS - Inspection :*
08/11/2010 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SIGN TO BE GROUNDED/BONDED. ALL METAL SIGN AND LETTERS NEC 600.7
2) HAVE OPEN BOX SPLICES. USE APPROVED WIRING METHODS AND JUNCTION BOXES. CANNOT USE FLEXIBLE CORDS AS PERMANENT WIRING METHOD. ONLY PORTABLE SIGNS TO BE CORD AND PLUG CONNECTED
3) PROVIDE DISCONNECTING MEANS 600.6 (A) NEC
4) NEED MANUFACTURES MARKING LOABEL NEC 600.4