Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2010 | FIRE - FINAL | Approved | Approved 10/28/10 | |
| 07/14/2010 | FIRE - FINAL | Denied | Not approved 7/14/10 1.) Need a sign over the main exit door that reads, "DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED". 2.) Potable fire extinguisher past due for annual inspection. Must be labled 3.) Remove the slide-bolt from the rear exit door. 4.) Remove the double-cylinder lock from rear security door and replace with a thumb-turn lock 5.) Address numbers for the building must be minomun of 12" to 15". |
|
| 07/13/2010 | FIRE - FINAL | Denied | No Access |