Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2010 | FIRE - FINAL | Approved | Approved 6/22/10 | |
| 06/07/2010 | FIRE - FINAL | Denied | 1. Annual fire sprinkler report and 5 year check valve test are past due. 2. Painted sprinkler heads must be replaced. 3. Sprinkler system control valve must be supervised. 4. Numerous electrical hazards needs service/repair. 5. Light upstairs shall be serviced/repaired or removed. 6. Pressure cylinders must be secured. 7. Sliding locking latches must be removed from all egress doors. 8. Extension cords shall not be used as permanent wiring. 9. Electrical blanks required in electrical service panel. 10. Internally illuminated exit signs are required. 11. Emergency egress lighting reqqired. 12. security grill shall be locked in the open position. 13. Fire extinguishers shall be serviced/repaired and mounted. 14. Lable 55 gallon barrels. |