Permit: T10OT00992

Parcel: 12412070A


Addresses:

1502 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10OT00992

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2010 FIRE - FINAL Approved Approved 6/11/10
05/06/2010 FIRE - FINAL Denied Not approved 5/6/10
1.) The thumb-turn lock in the # 1 office is hard to turn. Must be readily openable without the use of special effort or special knowledge.
2.) Repair burnt out Exit signs.
3.) Replace missing cover plate. (back office next to copier)
4.) Fire extinguishers must be seviced annually. must be mounted and must be labled.
5.) Need a clear working space in the area around the electrical panel.( min.36")
6.) Replace the missing face plate on the electrical panel.
7.) Exit accesses/ pathways must remain clear of obstructions at all times.
8.) Lable the exterior storage room door,"ELECTRICAL".
9.) Need a sign on the lobby door (left side) that reads,"NOT AN EXIT".
10.) Need a thumb-turn lock for the gated area in the front of the building.
11.) Remove the accumulated combustible storage that is located in the front exterior storage room.