Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10OT00952
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2010 | FIRE - FINAL | Approved | Approved 6/9/10 | |
05/05/2010 | FIRE - FINAL | Denied | Not approved 5/5/10 1.) Replace all missing cover plates. 2.) The door leading into the warehouse, next to the bathrooms, needs a sign stating, "NOT AN EXIT" 3.) Same door but on the warehose side, also a "Not An Exit" sign, or must remove the cylinder lock and replace with a thumb-turn lock. 4.) Need palns and permit for the storage loft added in the warehouse or must remove the structure completely. 5.) Need a breaker blank for electrical panel, warehouse area. 6.) Secure the open wiring, per electrical code, that is located at the electrical panel. 7.) Must one of the locks from the security screen door located SW, corner in the warehouse. 8.) Must remove the keyed locks from both exit doors in the warehouse area and replace with thumb-turn locks. 9.) All doors must be readily openenable without the having to use special effort.(enterior doors hard to open) |