Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10OT00941

Parcel: 13804180C


Addresses:

617 W VALENCIA RD


Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T10OT00941

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2010 SIGN ELECTRIC Approved IVRS - Inspection :*
1) MANAGERS HAVE BEEN NOTIFIED OF HAZARDS AT PANELS
10/25/2010 SIGN ELECTRIC Denied IVRS - Inspection :
1) FILL UNUSED OPENINGS IN BACK OF LETTERS AND JUNCTION BOXES INSIDE SIGN
2) THHN CONDUCTORS TO BE ENCLOSED IN RACEWAY-3 SIDED COVER NOT A RACEWAY
3) MAINTAIN WORKING CLEARANCE IN FRONT OF PANELS 110.26