Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2010 | FIRE - FINAL | Approved | ||
| 05/07/2010 | FIRE - FINAL | Denied | 1. Remove dead bolt on North door which has panic hardware. 2. Electrical blank required on the center electrical panel. 3. Relocatable power tap shall be directly connected into permanent power supply. 4. Cover rear non-exit door on N/E side rear door. 5. Annual sprinkler test and 5 year check valve test past due. 6. Update portable fire extinguisher with current inspection tags. Note: Extinguishers were recently inspected but 2009 was punched instead of 2010 on inspectionj tag. |