Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2010 | FIRE - FINAL | Approved | Approved 8/25/10 | |
| 05/21/2010 | FIRE - FINAL | Denied | 1. Emergency egress lighting required. 2. Illuminated exit signs are required on main and rear exit doors. Exit signs shall stay illuminated for 90 minutes in case of power loss. 3. Electrical cover plates required on all electrical outlets. 4. Repair or replace damaged ceiling tiles. 5. Electrical blanks are required in electrical service panels X2. 6. Drop down bars and latch locks are not allowed. South/West room. |