Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2010 | FIRE - FINAL | Approved | ||
| 04/14/2010 | FIRE - FINAL | Denied | 1. OCC LOAD IS 83 FRONT EXIT DOOR OPENS INWARD. THIS DOOR NEEDS TO OPEN OUTWARD. 2. REAR EXIT DOOR NEEDS A DOOR KNOB SYLYE LATCH CAN NOT USE SLIDE BOLT LOCK. DEAD BOLT LOCKS SHALL BE THUMB STYLE AND NOT DOUBLE CYLINDER KEYED LOCKS. 3. OUTLETS SHALL HAVE COVER PLATES, NEED TO REPLACE MISSING PLATES OUTSIDE BACK AND INSIDE WORK AREA. 4. ADDRESS NUMBERS SHALL BE POSTED PER HANDOUT GIVEN 12 INCH NUMBERS. 5. FRONT DOOR SHALL BE LABEL WITH THE FOLLWING " THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUIPED" 1 INCH HIGH LETTERS. |
|
| 04/12/2010 | FIRE - FINAL | Denied | Denied- No access. |