Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2010 | FIRE - FINAL | Approved | Not approved 5/12/10 1.) Must secure all open wiring: a.) In the front of the building. b.) In the storage room, shop area. 2.) Need a thumb-turn lock for the storage room located in the shop area. 3.) Need a cover plate in the center room. 4.) Need address numbers for the building. Must be readily visible from thje street and must be a minimum of 15 inches high. 5.) Remove the pad lock from the front door. 6.) Remove the slide-bolt from the the front door. 7.) Provide a thumb-turn lock for the front door or a keyd lock, providing a sign over the fron door is provided. The sign must read,"DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED". |
|