Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2010 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 05/19/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950*3 1) NO WORK PROGRESS 2) WORK TO BE PERFORMED BY QUALIFIED ELECTRICIAN 3) A REFEE MAY BE ASSESED |
|
| 05/17/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONLY ONE CONDUCTOR PER TERMINAL LUG CONNECTIONS 2) RISER HARDWARE TO BE 1/4" MINIMUM 3) NEED GROUNDING BURCTRADE SYSTEM 4) CORRECTLY IDENTIFY UNDERGROUND CONDUCTOR 5) RECEPTACLES IN SHOP AREA TO E GFI PROTECTED 6) EXPOSED CONDUCTORS IN WALLS A) CABLE SHEATING TO EXTEND 1/4" INTOBOXS & PANELS B) RACEWAYS TO BE CONTIUOUS BOX TO BOX 7) 2) RISER HARDWARE TO BE 1/4 " MINIMUM 3) NEED GROUNDING ELECTRODE SYSTEM 4) CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 5) RECEPTACLES IN SHOP AREA TO BE GFI PROTECTED 6) EXPOSED CONDUCTORS IN WALLS A) CABLE SHEATING TO EXTEND 1/4" INTO BOXS & PANELS B) RACEWAYS TO BE CONTINUOUS BOX TO BOX 7) FILL UNUSED OPENINGS WITH BOXES & PANELS 8( NEW FIXTURES IN SHOP TO BE FULLY ENCLOSED 511.7 (B) (1) (B) *WORK TO BE DONE BY A QUALIFIED ELECTRICIAN |