Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2010 | SIGN ELECTRIC | Approved | 1) PROVIDE AN EFFECTIVE GROUND FAULT PATH FOR LETTERS | |
| 05/18/2010 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED MARKING LABEL 600.4 2. SWITCH TO BE CAPABLE OF BEING LOCKED OUT 600.6 3. SIGN CONTRACTOR TO BE PRESENT TO PROVIDE ACCESS TO LETTERS TO INSPECT MOUNTING & BONDING 600.7 |