Permit: T10OT00589

Parcel: 12602004A


Addresses:

4646 E SPEEDWAY BL

Inspection Status: Cancelled

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
03/23/2010 FIRE - FINAL Cancelled IVRS - RI canceled
03/23/2010 FIRE - FINAL Approved Approved 3/23/10
03/17/2010 FIRE - FINAL Denied Not approved 3/17/10
1.) Sign over main door reading."DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED".
2.) Replace the thumb-turn lock on main door. Lock hard to open.
3.) Replace missing cover plate. office area.
4.) Replace burnt receptical located in the break room.
5.) Any storage under stairway is prohibited.
6.) Provide large sign in shop area where flammable liquids are stored.
7.) Need approved, accurate floor plans.
8.) Need permit for AGT in shop area.
9.) Need directional exit signs directing path to rear exit from the shop areas.
10.) Extinguishers must be labled.
11.) Secure walking surface over the lobby area.
12.) Provide "NO SMOKING" for shop areas.
13.) Remove the pad lock from the compressor room door.
14.) Remove all empty 55 gallon containers or lable them EMPTY".
15.) Need access to outside metal storage stuctures.
16.) ADDED AFTER LEAVING PROPERTY NOT ON OWNERS COPY, Must lable north east door in shop area, on exterior side, "DOOR BLOCKED".