Inspection History Details
Inspection Status: Cancelled
Inspection History: SIGN ELECTRIC
Permit Number - T10OT00524
Inspection Description - SIGN ELECTRIC
Inspection Status - Cancelled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2010 | SIGN ELECTRIC | Cancelled | IVRS - RI canceled | |
05/10/2010 | SIGN ELECTRIC | Approved | IVRS - Inspection :* 1) OK SIGNS |
|
05/06/2010 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) DRYWALL SCREWS NOT ALLOWED FOR MOUNTING OF OTHER THAN DRYWALL 2) FINISH #6 OF PREVIOUS INSPECTION 3) LENGTH OF SECONDARY CONDUCTORS 600.32 (5) (1) 4) USE AOPPROVED FITTINGS WITH SEAL TITE AND SUPPORT |
|
04/28/2010 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CANNOT USE DRYWALL OR WOOD SCREWS TO MOUNT LETTERS USE #10'S AS PER PLANS 2) GROUNDING TO BE PER 250.8 3) MAINTAIN 1 1/2" CLEARANCE FOR GROUND WIRE TO GTO RACEWAY 4) TIGHTEN LOOSE FITTINGS 5) NEED SERVICE WALK WAY 600.22 6) NEED SERVICE LIGHT 600.6 & 210.70 7) SUPPORT FLEX 8) CHECK ROOF SIGN NEXT TIME |